Receiver
Flash Steam
Diameter
up to ~
mm (in)
kg/h
(Length: 1 m)
25
80
50
100
75
125
100
150
150
200
200
200
300
250
400
300
500
350
700
400
800
450
1000
500
1100
500
1400
550
1500
600
Amount of
Condensate
kg/h
1000 or less
1500
2000
3000
6000
10000
NOTE: When amount of flash steam and condensate are between two values in the table, select
the larger value (one line below).
Vented Receiver Table - 1
(For atmospheric, open system installations)
Vent Line
Diameter
mm (in)
(3)
25
(1)
(4)
50
(2)
(5)
50
(2)
(6)
80
(3)
(8)
80
(3)
(8)
100
(4)
(10)
125
(5)
(12)
125
(5)
(14)
150
(6)
(16)
200
(8)
(18)
200
(8)
(20)
200
(8)
(20)
250
(10)
(22)
250
(10)
(24)
250
(10)
Vented Receiver Table - 2
(For atmospheric, open system installations)
Receiver
Diameter
mm (in)
(Length: 1 m)
(3)
80
(4)
100
(5)
125
(6)
150
(8)
200
(10)
250
— 15 —
Receiver
Flash Steam
Diameter
up to ~
in
lb/h
(Length: 3.5 ft)
50
75
100
200
300
400
600
10
800
12
1000
14
1400
16
1600
18
2000
20
2200
20
2800
22
3000
24
Receiver
Amount of
Diameter
Condensate
lb/h
(Length: 3.5 ft)
2200 or less
3300
4400
6600
13000
22000
Vent Line
Diameter
in
3
1
/
4
1
1 2
4
2
/
6
2
1 2
8
3
8
4
4
6
6
8
8
8
10
10
10
in
3
4
5
6
8
10