Closed System Piping (Steam System Example) - TLV PowerTrap GP14-B Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Q
Condensate Amount
Filling Head
A
Pm
Motive Medium Supply Pressure
Pb
Back Pressure
Si
Condensate Inlet Pipe
So
Condensate Outlet Pipe
Sr
Condensate Recovery Line
Sm
Motive Medium Supply Pipe
Se
Exhaust Pipe

Closed System Piping (Steam System Example)

Motive
Medium
Rm
Sv
Se
Pump
Exhaust
Power
Trap
NOTE: Pipe the discharge to a
safe area such as a pit.
**If the pressure at the PowerTrap inlet exceeds the pressure at the PowerTrap outlet, make sure to install
a steam trap at the PowerTrap outlet. (Steam will blow if no steam trap is installed.)
Make sure the pipe between the PowerTrap and the steam trap is as short and thick as possible.
There should be no rise in piping between the PowerTrap and the steam trap.
Select the steam trap based on the pump discharge capacity of the PowerTrap. Consult TLV for details.
NOTE: This sketch is for explanation purposes only and is not intended as an installation design.
In closed system applications, the motive medium must be compatible with the liquid
being pumped. If a non-condensable gas such as air or nitrogen is used as the motive
medium, please consult TLV for assistance.
Q
Condensate Amount
A
Filling Head
Pm
Motive Medium Supply Pressure
Pb
Back Pressure
Si
Condensate Inlet Pipe
So
Condensate Outlet Pipe
Sr
Condensate Recovery Line
Sm
Motive Medium Supply Pipe
Se
Exhaust Pipe
SP
Steam Trap on the Power Trap outlet
Sv
Vent Pipe
Overflow Pipe
Sf
Dh
Condensate Receiver
Ci
Condensate Inlet Check Valve
Condensate Outlet Check Valve
Co
Ki
Condensate Inlet Strainer
Km
Motive Medium Strainer
Motive Medium Pressure
Rm
Reducing Valve
Motive Medium
Supply Pressure Pm
Steam for
Heating
Sm
*
Ca
La
Condensate
Amount Q
Condensate
Reservoir Dh
St
Vm
Km
Vi
Ci
Si
Ki
Sp**
Vo
Co
Sv
Vent Pipe
Dh
Condensate Reservoir
Ci
Condensate Inlet Check Valve
Co
Condensate Outlet Check Valve
Ca
Check Valve for Air Vent
La
Air Vent (for Steam)
Ki
Condensate Inlet Strainer
Km
Motive Medium Strainer
Pi
Equipment Pressure
Pi
St
Vi
Vo
Vm
Ve
Vb
Temperature Controller
Va
Back
Pressure
Pb
So
When the rise in piping is 30 m (100 ft) or farther from the
PowerTrap, installation of check valve is recommended
for the prevention of return water hammer.
Rm
St
Vi
Vo
Vm
Ve
Va
Vb
— 9 —
Equipment Pressure
Steam Trap on Drip leg
Valve on Condensate Inlet Pipe
Valve on Condensate Outlet Pipe
Valve on Motive Medium Supply Pipe
Valve on Exhaust Pipe
Blowdown Valve
Equipment
Pressure
Pi
Sr
Steam-using
Equipment
Condensate
Recovery
Line
Backflow
Water
Hammer
Prevention
Check Valve
Motive Medium Pressure
Reducing Valve
Steam Trap on Drip Leg
Valve on Condensate Inlet Pipe
Valve on Condensate Outlet Pipe
Valve on Motive Medium Supply Pipe
Valve on Exhaust Pipe
Valve for Air/Gas Discharge
Blowdown Valve