Device informa-
For displaying the settings that will be of relevance to a power supply company. The val-
tion
ues shown will depend on the country setup or the device-specific settings of the
inverter.
Display area
General:
Country-specific set-
ting:
MPP Tracker:
Grid monitoring:
Grid voltage limits
inner limit value:
36
General / Country-specific setting / MPP tracker / Grid monit-
oring / Grid voltage limits / Grid frequency limits / Q-mode /
AC power limit / AC voltage derating / Fault Ride Through
Device type - the exact name of the inverter
fam. - inverter family of the inverter
serial number - serial number of the inverter
Setup - specified country setup
Version - version of country setup
Origin activated - indicates that the normal country-specific
setup is activated.
Alternat. activated - indicates that the alternative country-spe-
cific setup is activated (for Fronius Symo Hybrid only)
Group - group for updating the inverter software
Tracker 1 - indicates the set tracking behaviour (MPP AUTO /
MPP USER / FIX)
Tracker 2 (only on Fronius Symo except for Fronius Symo
15.0-3 208) - indicates the set tracking behaviour (MPP
AUTO / MPP USER / FIX)
GMTi - Grid Monitoring Time - start-up time of the inverter in
sec (seconds)
GMTr - Grid Monitoring Time reconnect - reconnection time in
sec (seconds) after a grid fault
ULL - U (voltage) Longtime Limit - voltage limit value in V
(volts) for the 10-minute average voltage value
LLTrip - Longtime Limit Trip - trip time for ULL monitoring,
how fast the inverter should switch off
UImax - upper inner grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the upper
inner grid voltage limit value in cyl*
UMin - lower inner grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the lower
inner grid voltage limit value in cyl*
*cyl = grid periods (cycles); 1 cyl corresponds to 20 ms at 50
Hz or 16.66 ms at 60 Hz