The Basic menu is used to set the following parameters, which are important for
Basic menu
installing and operating the inverter:
MPP Tracker 1 / MPP Tracker 2
-
-
-
-
-
USB log book
Activates or deactivates the function for saving all error messages to a USB flash drive
AUTO / OFF / ON
Input signal
-
SMS / relay
-
-
Insulation setting
-
-
TOTAL Reset
in the LOG menu item, resets the max. and min. voltage values and the max. power of
feeding in to zero.
Once values have been reset, this action cannot be undone.
To reset the values to zero, press the 'Enter' key.
"CONFIRM" is displayed.
Press 'Enter' again.
The values are reset and the menu is displayed
42
MPP Tracker 2: ON / OFF (only for devices with multiple MPP trackers)
DC operating mode: MPP AUTO / FIX / MPP USER
•
MPP AUTO: normal operating status; the inverter automatically searches for
the ideal operating point
•
FIX: for entering a fixed DC voltage at which the inverter will operate
•
MPP USER: for entering a lower MP voltage above which the inverter will
search for its ideal operating point
Dynamic Peak Manager: ON / OFF
Fixed voltage: for inputting a fixed voltage (80 - 800 V)
MPPT start voltage: for inputting the start voltage (80 - 800 V)
How it works: Ext Sig. / S0-Meter / OFF
only with the Ext Sig. function selected:
•
Triggering method: Warning (warning shown on display) / Ext. Stop (inverter
switches off)
•
Connection type: N/C (normally closed contact) / N/O (normally open con-
tact)
Event delay
for inputting the time delay after which an SMS is sent or the relay is to switch
900 - 86,400 seconds
Event counter:
for entering the number of events that lead to signalling:
10 - 255
Insulation warning: ON / OFF
Threshold warning: for entering a threshold that leads to a warning