Logging interval
Activate / deactivate the USB logging function and specify a logging interval
Unit
Setting range
Factory setting
30 min.
20 min.
15 min.
10 min.
5 min.
No log
IMPORTANT! In order for the USB logging function to work correctly the time must be
set correctly. Setting the time is discussed in the section "Menu items in the Setup menu"
- "Clock".
Relay (floating
Status codes (state codes), the status of the inverter (e.g. feeding energy into the grid) or
contact switch)
Energy Manager functions can be displayed using the floating switch contact (relay).
Setting range
* these are only shown if the "E-Manager" function has been activated under "Relay
mode".
Relay mode
The following functions can be shown using relay mode:
-
-
-
Setting range
Factory setting
Minutes
30 min. / 20 min./ 15 min./ 10 min./ 5 min./ No log
30 min.
The logging interval is 30 minutes; every 30 minutes new log-
ging data will be saved to the USB flash drive.
The logging interval is 5 minutes; every 5 minutes new log-
ging data will be saved to the USB flash drive.
No data is saved
Relay mode / Relay test / Switch-on point* / Switch-off point*
Alarm function (Permanent / ALL / GAF)
Active output (ON / OFF)
Energy Manager (E-Manager)
ALL / Permanent / GAF / OFF / ON / E-Manager
ALL
Alarm function:
ALL / Per-
Switching the floating switch contact for permanent and temporary
manent:
service codes (e.g. brief interruption to energy being fed into the
grid, a service code occurs a certain number of times a day - can be
adjusted in the "BASIC" menu)