Fronius Primo 3.0-1 Instructions De Service page 46

Masquer les pouces Voir aussi pour Primo 3.0-1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code
Description
451
Memory error detected
Communication error
452
between the processors
453
Short-term grid voltage error
Short-term grid frequency
454
error
456
Anti-islanding function is no
longer being implemented
correctly
457
Grid relay sticking
Error when recording the
459
measuring signal for the insu-
lation test
Reference voltage source for
the digital signal processor
460
(DSP) is working out of toler-
ance
461
DSP data memory error
462
Error during DC feed monitor-
ing routine
463
Reversed AC polarity, AC
connector inserted incorrectly
474
RCMU sensor faulty
Solar module ground, insula-
tion fault (connection
475
between solar module and
earth)
476
Driver supply voltage too low
479
Intermediate circuit voltage
relay is switched off
Functional incompatibility
(one or more PC boards in
480,
the inverter are not compat-
481
ible with each other, e.g. after
a PC board has been
replaced)
46
Behaviour
The inverter will automatically
attempt to connect again and, if
possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid.
The inverter is not feeding any
energy into the grid.
The inverter will automatically
attempt to connect again and, if
possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid.
Remedy
If the status code is displayed
all the time: Notify a Fronius-
trained service engineer
Notify a Fronius-trained service
engineer
If this status code keeps recur-
ring, contact your system engin-
eer
If the status code is displayed
all the time: Notify a Fronius-
trained service engineer
Update inverter firmware;
If the status code is displayed
all the time: Notify a Fronius-
trained service engineer