Item
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Explanation of
Various wiring variants can be connected to the multifunction current interface. However,
the multifunction
these cannot be operated simultaneously. For example, if an S0 meter is connected to
current interface
the multifunction current interface, it is not possible to connect a signal contact for the
surge protection device (or vice versa).
Pin 1 = measurement input: max. 20 mA, 100 Ohm measurement resistor (load imped-
ance)
Pin 2 = max. short circuit current 15 mA, max. open circuit voltage 16 V DC or GND
Wiring diagram variant 1: Signal contact for surge protection device
Depending on the setting in the Basic menu (Signal Input submenu), the DC SPD option
(surge protection device) either outputs a warning or an error on the display. Further
information on the DC SPD option can be found in the Installation Instructions.
Description
IN Fronius Solar Net connection / interface protocol IN
OUT Fronius Solar Net connection / interface protocol
"Fronius Solar Net" / interface protocol input and output for connecting to other
DATCOM components (e.g. inverter, Fronius sensor box, etc.)
If several DATCOM components are linked together, a terminating plug must
be connected to every free IN or OUT connection on a DATCOM component.
For inverters with a Fronius Datamanager plug-in card, two terminating plugs
are supplied with the inverter.
The "Fronius Solar Net" LED
indicates whether the Fronius Solar Net power supply is available
The "Data transfer" LED
flashes while the USB flash drive is being accessed. The USB flash drive must
not be removed while recording is in progress.
USB A socket
for connecting a USB flash drive with maximum dimensions of
65 x 30 mm (2.6 x 2.1 in.)
The USB flash drive can function as a datalogger for any inverter that it is con-
nected to. The USB flash drive is not included in the scope of supply of the
inverter.
Floating switch contact (relay) with mating connector
Max. 250 V AC / 4 A AC
Max. 30 V DC / 1 A DC
Max. 1.5 mm² (AWG 16) cable cross-section
Pin 1 = NO contact (normally open)
Pin 2 = C (common)
Pin 3 = NC contact (normally closed)
For a more detailed explanation, please see the "Menu items in the Setup
menu / Relay" section.
Use the mating connector supplied with the inverter to connect to the floating
switch contact.
Fronius Datamanager with WLAN antenna
or
cover for option card compartment
Cover for option card compartment
11