The INFO menu item
Measurement val-
PV Iso.
ues
Insulation resistance for the photovoltaic system
U PV 1/U PV 2
Current DC voltage on the terminals, even if inverter is not feeding any energy (from 1st or
2nd MPP tracker)
GVDPR
Grid voltage-dependent power reduction
Fan #1
Target output of fan in percent
LT Status
The status display of the last error that occurred in the inverter can be shown.
IMPORTANT! Status codes 306 (Power low) and 307 (DC low) appear naturally every
morning and evening due to low solar irradiance. These status codes are not the result of
a fault.
-
-
-
Grid Status
The last 5 grid errors that occurred can be displayed:
-
-
-
RCMU
RCMU = Residual Current Monitoring Unit
The inverter is equipped with an RCMU according to Austrian standard ÖVE/ÖNORM E
8001-4-712.
It monitors residual currents from the solar module to the inverter grid connection and dis-
connects the inverter from the grid when an improper residual current is detected.
Additional residual current protection may be needed depending on the installation's pro-
tection system or the requirements of the utility company. In this case, use a type B residual
current circuit breaker with a release current of at least 100 mA.
Device Informa-
Used to display settings relevant to a power supply company. The displayed values de-
tion
pend on the respective country setup or device-specific inverter settings.
Display range
38
After pressing the "Enter" key, the power stage set status and the last error that oc-
curred are displayed
Use the "up" and "down" keys to scroll through the list
Press the "Back" key to exit the status and error list
After pressing the "Enter" key, the last 5 grid errors that occurred are displayed
Use the "up" and "down" keys to scroll through the list
Press the "Back" key to exit the grid error display
General/Country-specific setting/MPP tracker/Grid monitoring/
Grid voltage limits/Grid frequency limits/Q-mode/AC output limit