Device Information - Fronius Primo 3.0-1 Instructions De Service

Masquer les pouces Voir aussi pour Primo 3.0-1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Device informa-
For displaying the settings that will be of relevance to a power supply company.
tion
The values shown will depend on the country setup or the device-specific set-
tings of the inverter.
Display area
General:
Country-specific
setting:
MPP Tracker:
Grid monitoring:
Grid voltage limits
inner limit value:
General / Country-specific setting / MPP tracker / Grid
monitoring / Grid voltage limits / Grid frequency limits /
Q-mode / AC power limit / AC voltage derating / Fault
Ride Through
Device type - the exact name of the inverter
fam. - inverter family of the inverter
serial number - serial number of the inverter
Setup - specified country setup
Version - version of country setup
Origin activated - indicates that the normal country-
specific setup is activated.
Alternat. activated - indicates that the alternative coun-
try-specific setup is activated (for Fronius Symo Hybrid
only)
Group - group for updating the inverter software
Tracker 1 - indicates the set tracking behaviour (MPP
AUTO / MPP USER / FIX)
Tracker 2 (only on Fronius Symo except for Fronius
Symo 15.0-3 208) - indicates the set tracking behaviour
(MPP AUTO / MPP USER / FIX)
GMTi - Grid Monitoring Time - start-up time of the in-
verter in sec (seconds)
GMTr - Grid Monitoring Time reconnect - reconnection
time in sec (seconds) after a grid fault
ULL - U (voltage) Longtime Limit - voltage limit value in
V (volts) for the 10-minute average voltage value
LLTrip - Longtime Limit Trip - trip time for ULL monitor-
ing, how fast the inverter should switch off
UImax - upper inner grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the up-
per inner grid voltage limit value in cyl*
UMin - lower inner grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the
lower inner grid voltage limit value in cyl*
*cyl = grid periods (cycles); 1 cyl corresponds to 20 ms
at 50 Hz or 16.66 ms at 60 Hz
39

Publicité

Table des Matières
loading

Table des Matières