Note: If the control panel PGM output connected to the 3G4010CF/LE4010CF input latches
(remains closed) after an alarm has occurred, the 3G4010CF/LE4010CF input will remain active.
The latched PGM output must be reset or future alarms will not be reported via the zone
input of the 3G4010CF/LE4010CF and additional alarms may be triggered when the 3G4010CF/
LE4010CF is locally or remotely restarted. Please contact panel vendor for details on how to
reset the control panel PGM.
Figure 3: 3G4010CF/LE4010CF Module Wiring Diagram - Standalone Configuration
Figure 4: Power Supply Wiring Diagram
These outputs shall be connected to zone inputs of an alarm control panel in order to provide
the required trouble supervision (visual and audible indication required at the control panel). The
outputs are active low (switched to ground) and can be connected to a control panel directly or by
using a listed supervision relay (suggested model: DSC, RM-2 or RM1C).
3G4010CF / LE4010CF Installation manual
33