Connecting the 3G4010CF/LE4010CF
(1) Earth Ground - This terminal must be connected to the Mains Earth, in order to comply with the
Telecommunications Network Safety Standards (Overvoltage Protection Requirements).
TIP (2) / RNG (3) External Telephone Line - These terminals must be connected directly to the
incoming telephone line.
T1 (4) / R1 (5) Internal Telephone Line - These terminals must be connected to the TIP and RING
of the control panel.
COM (6,12) Common - This terminal is connected internally to Power Ground.
PGM1 (7), PGM2 (8), PGM3 (9), PGM4 (10) Programmable Open-collector Outputs - These outputs
can be activated by programmed events. Refer to 'Activating the Outputs' for details. The
maximum current sink of each output must not exceed 50mA.
AUX+ (11) Auxiliary Output - 9 to 14 VDC Output, 500mA PTC Protected.
Note: Electrical current drawn from this terminal is drawn directly from the power supply. This
must be added to the 3G4010CF/LE4010CF current when determining the total draw on the
host panel or power supply.
Z1-Z4 (13-14-15-16) Programmable Inputs - These terminals can be set up to trigger events. Refer
to 'Inputs' for details.
+12V (19), -12V (20) Device Power Supply - These terminals must be connected to the output of
the power supply [10]. When the connections are completed, connect the Red and Black wires [12]
to 12V, 7Ah battery [13].
Power supply module
AC - Supervised input, connect the secondary of the transformer to these terminals. Connect the
primary of the transformer to a dedicated electrical circuit.
DC IN (17), (18) - Special application output circuit, power limited, connect to 3G4010CF/LE4010CF
power input circuit. Connect the +12V output to +12V input on the 3G4010CF/LE4010CF module.
COM output to the - 12V input on the 3G4010CF/LE4010CF module.
ACT (AC Trouble) - This open collector output activates when an AC Trouble is detected: Rated
50mA.
Note: AC Trouble output shall be connected to an input on the alarm control panel that
provides immediate local annunciation and delayed remote transmission for 1 to 3 hours. If
such input is not able to provide the delay for AC loss transmission, input 1 of the 3G4010CF/
LE4010CF can be used. When Input 1 is triggered, the 3G4010CF/LE4010CF will immediately
announciate an AC trouble by flashing the RED status LED 9 times, and will delay the AC loss
event transmission by one hour.
LBT (Battery Trouble) - This open collector output activates when a Battery Trouble condition is
detected: Rated 50mA.
TEST (Charger Trouble) - This open collector output activates when the charging circuit is in a
trouble condition: Rated 50mA.
These outputs shall be connected to zone inputs of an alarm control panel in order to provide
the required trouble supervision (visual and audible indication required at the control panel). The
outputs are active low (switched to ground) and can be connected to a control panel directly or by
using a listed supervision relay (suggested model: DSC, RM-2 or RM1C relay).
3G4010CF / LE4010CF Installation manual
16