Standard battery capacity
The calculation for battery capacity is based on 200mA standby current for 24 hours plus a five
minute alarm at 400mA or 600mA (if the 4 PGM outputs are also activated) The requirements are as
follows:
200mA x 24h = 4800mAh capacity for standby
400mA x 5/60h= 33.33mAh capacity for alarm condition
Total = 4833.33 mAh needed for 24h and five minutes alarm transmission. The supplied battery is
7Ah.