Note: For UL/ULC listed installations, End of Line supervision must be used for all inputs.
Note: When the 3G4010CF/LE4010CF is configured in land line mode, these inputs should be
restricted to monitoring of trouble conditions.
Outputs
The 3G4010CF/LE4010CF has four programmable outputs to activate in response to the associated
events. Refer to the 3G4010CF/LE4010CF Wiring Diagram at the back of this manual.
Activating the outputs
The 3G4010CF/LE4010CF has four open collector outputs capable of a maximum of 50mA. Internal
events on the3G4010CF/LE4010CF can trigger the outputs to turn on an LED or activate an input on
the host panel. The default settings are as follows.
OUTPUT 1: Landline Trouble - Output is normally high and switches to ground when the telephone
line is down.
OUTPUT 2: Cellular Module or Network Trouble - Output is normally high and switches to ground
when the 3G4010CF/LE4010CF cannot communicate with the network.
OUTPUT 3: Power Supply or Battery Trouble - Output is normally high and switches to ground
when a problem with the power source is detected.
OUTPUT 4: General Module Trouble - Output is normally low and switches to high when a Cellular
Network Trouble, Power Supply/Battery Trouble, and/or a Failure to Communicate (FTC) trouble is
detected.
Note: PGM4 must be connected to the control panel as shown in Figure 4 (Residential
applications) or Figures 8-9 (Commercial applications). Program the control panel input Zone/
Point as 24hr 'Supervisory' with keypad only notification when activated. Output 4 on the
3G4010CF/LE4010CF must be set as 'Active High'.
Note: Once an output has been activated automatically, it will not restore until all the causes
of activation are cleared.
Reporting codes
Table 6: 3G4010CF/LE4010CF reporting codes
Reporting codes
CID
Zone 1 Activation
E301 991
Zone 1 Restoral
R301 991
Zone 2 Activation
E200 992
Zone 2 Restoral
R200 992
Zone 3 Activation
E110 993
Zone 3 Restoral
R110 993
Zone 4 Activation
E300 994
Zone 4 Restoral
R300 994
PSTN Line Down
E351 000
PSTN Line
R351 000
Restoral
3G4010CF / LE4010CF Installation manual
SIA
Programmable
AT 991
YES
AR 991
YES
FS 992
YES
FV 992
YES
FA 993
YES
FH 993
YES
YX 994
YES
YZ 994
YES
LT 000
FIXED
LR 000
FIXED
Comments
AC Loss*
AC Loss Restore *
Fire Supervisory*
Fire Supervisory
Restore*
Fire *
Fire Restore *
System Trouble *
System Trouble
Restore *
Telco 1 Fault
Telco 1 Fault
Restore
21