Hardware default
A hardware default updates the unit with the latest configuration from C24 Communications if:
The device is programmed incorrectly.
The unit was installed at a different location and then relocated to a new site.
The SIM card is swapped.
To perform the hardware default, follow these steps:
1. Power down the unit (remove primary DC power and remove the backup battery) and remove
all connections to Zone1, Zone 2, PGM1 and PGM..
2. Connect a wire between Z2 (terminal 14) and PGM2 (terminal 8)or Z1 (terminal 13) and PGM1
(terminal 7).
3. Power up the radio by connecting the battery (if present) first and then primary DC power.
4. Wait for 20 seconds and then completely power down the unit.
5. Disconnect the wire between the Zone and PGM terminals.
Note: Failure to perform hardware default will result in the unit transmitting with the
previously programmed configuration.
Communicator reset/update
The device firmware can be updated over Cellular or PC-Link:
Table 7: Firmware update begins
Red
ON
When the firmware update begins, all LEDs are ON.
Table 8: Firmware update process
Red
FLASH ON
OFF
OFF
OFF
FLASH ON
OFF
OFF
OFF
During the firmware update process, the LEDs cycle individually in a chaser pattern (different from
the Advanced Carrier Selection pattern). The unit automatically restarts after a successful update.
Note: Several resets occur during a single firmware update session.
Note: The unit re-requests programming after a firmware update. The version number is
updated and viewable via C24 Communications.
Note: The 3G4010CF/LE4010CF must not be powered down during a firmware update.
3G4010CF / LE4010CF Installation manual
Blue
ON
Blue
OFF
FLASH ON
OFF
OFF
OFF
FLASH
OFF
OFF
Yellow / Green (high)
ON
Yellow / Green (high)
OFF
OFF
FLASH ON
OFF
OFF
OFF
FLASH
OFF
Yellow / Green (low)
ON
Yellow / Green (low)
OFF
OFF
OFF
FLASH ON
OFF
OFF
OFF
FLASH
23