Approvals information
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to the specific values or not used at all as
indicated below.
Program feature or
option
Supervision
Inputs / outputs
SMS remote control
Note: This product has been tested in accordance with UL 864 9th edition. According to this
edition of the standard, the supervision window for reporting single-technology communicator
trouble shall be set to five minutes. However, the product can be installed in accordance with
the requirements of NFPA72 2013 edition, which allows for a 60-minute supervision window.
Note: Encryption shall be enabled for active communications.
Note: For using Private, Corporate and High Speed Data Networks: Network access and
domain access policies shall be set to restrict unauthorized network access, and "spoofing" or
"denial of service" attacks. Select the internet service providers that have redundant servers/
systems, back-up power, routers with firewalls enabled and methods to identify and protect
against "denial of service" attacks (i.e., "spoofing"). For UL Res-idential Fire and Burglary
installations, the 3G4010CF/LE4010CF is listed as a sole means of communication or as a back
up when used in conjunction with a POTS line (dialer).
For ULC Residential Fire and Burglary installations, the 3G4010CF/LE4010CF is listed as a sole
means of communication or as a back up when used in conjunction with a POTS line (dialer).
For UL Commercial Burglary installations, the 3G4010CF/LE4010CF is listed as a sole means of
communication (supervision window of 200s required at monitoring station) or as a back-up when
used in conjunction with a POTS line (dialer). The 3G4010CF/LE4010CF shall be powered from any
compatible listed control unit or compatible listed power supply that complies with the ratings
specified on page 1. The power supply shall be listed for burglary applications and provide a
minimum of 4 hours standby power capabilities. An example of a suitable listed compatible control
unit is the DSC Model HS2128 with an AUX output rated 11.1 - 12.6 VDC . An example of a suitable
listed power supply is DSC Model HSM2204 with an AUX output rated 11.6 - 12.6 VDC.
For ULC Commercial Burglary Monitoring Installation the 3G4010CF/LE4010CF can be used in the
following configurations:
Active communication system with 180 seconds supervision and heartbeat sent to signal
receiving centre every 90 seconds.
Passive communication system line security P1 (single communication channel) or line security
P2 (used as backup in conjunction with another communication path (e.g. DACT)). There is no
heartbeat sent in this configuration, only periodic test transmissions.
Every 24 hours, a test transmission must be sent to the signal receiving centre over each
communication path. Each communication path shall be monitored for integrity (DACT shall
have line monitoring enabled and 3G4010CF/LE4010CF shall have cellular connection supervision
Permitted in UL 864
Yes
Yes
No
Possible settings
5 minutes / 60 minutes 5 minutes
Fire / burglary signals
Enable / Disable
3G4010CF / LE4010CF Installation manual
Settings permitted in
UL 864
Fire related signals
only
Disable
6