Table 11: Red/Blue LED troubles
Number of flashes
2
3
OFF
OFF
Trouble type
Battery Trouble
Input Power Trouble
3G4010CF / LE4010CF Installation manual
Trouble notes
If a battery is
not used in the
installation,
ensure that the
"Internal Battery
Connected" is not
selected in C24
Communications.
If a battery is used
in the installation,
verify the battery
is connected
properly.
Measure the
battery under load
and verify it is
charged to at least
11.8VDC. If not,
wait at least 1 hour
for the battery to
charge.
Remove the battery
and measure the
voltage; the voltage
should be at least
11.8VDC.
Verify the input DC
supply is rated at
13.8 VDC at 180mA
minimum.
Replace battery
Ensure the power
source connected
to the 3G4010CF/
LE4010CF is providing
13.8 VDC at 180 mA.