Note: The 3G4010CF/LE4010CF is unable to decode pulse dialing.
If the panel is programmed for Contact ID format:
•
The 3G4010CF/LE4010CF sends the required Contact ID dual-tone handshake to the panel.
•
After receiving the handshake, the control panel transmits an alarm message in Contact ID
format.
•
The 3G4010CF/LE4010CF decodes and transforms the Contact ID digits into an IP packet and
sends it to the central station receiver over the cellular network.
•
The central station receiver acknowledges the alarm and sends a command to the 3G4010CF/
LE4010CF to generate the corresponding 1400Hz Kiss-off signal for a minimum of 800
milliseconds.
After the 3G4010CF/LE4010CF generates a Kiss-off signal, it sends the next alarm or, if no further
alarms need to be sent, the control panel goes on-hook.
If the panel is programmed for SIA (300 baud) format:
•
The 3G4010CF/LE4010CF sends the required SIA handshake to the panel.
•
After receiving the handshake, the control panel transmits an alarm message in the SIA format.
•
The 3G4010CF/LE4010CF decodes and transforms the SIA events into an IP packet that it sends
to the central station receiver over the cellular network.
•
The central station's receiver acknowledges the alarm and sends a command to the 3G4010CF/
LE4010CF to generate the corresponding 2025Hz kiss-off signal for a minimum of one second.
•
After the 3G4010CF/LE4010CF generates a kiss-off signal, it sends the next alarm or, if no further
alarms need to be sent, the control panel goes on hook.
Note: The 3G4010CF/LE4010CF automatically adjusts the order of the handshakes based on
the last format the control panel used to transmit an event.
Inputs
The 3G4010CF/LE4010CF has four inputs that can be used to trigger specific communications.
These events transmit using the Contact ID or SIA format with Inputs 1-4 reporting as [991] to [994]
respectively.
Default settings are:
INPUT 1- AC LOSS
INPUT 2 - FIRE SUPERVISORY
INPUT 3 - FIRE ALARM
INPUT 4 - SYSTEM TROUBLE
Inputs can be configured as follows:
Normally Open - input activates when a short condition is detected between the terminal and COM
Normally Closed - input activates when an open condition is detected between the terminal and
COM
Single End of Line - input activates when a short or open condition is detected between the
terminal and COM and restores when a 5.6Kohm resistor is detected between the terminal and
COM.
Note: These inputs are programmable to communicate using either the Contact ID or SIA
format.
3G4010CF / LE4010CF Installation manual
20