Note: The 3G4010CF/LE4010CF is unable to decode pulse dialing.
If the panel is programmed for Contact ID format:
The 3G4010CF/LE4010CF sends the required Contact ID dual-tone handshake to the panel.
After receiving the handshake, the control panel transmits an alarm message in Contact ID
format.
The 3G4010CF/LE4010CF decodes and transforms the Contact ID digits into an IP packet and
sends it to the central station receiver over the cellular network.
The central station receiver acknowledges the alarm and sends a command to the 3G4010CF/
LE4010CF to generate the corresponding 1400Hz Kiss-off signal for a minimum of 800
milliseconds.
After the 3G4010CF/LE4010CF generates a Kiss-off signal, it sends the next alarm or, if no further
alarms need to be sent, the control panel goes on-hook.
If the panel is programmed for SIA (300 baud) format:
The 3G4010CF/LE4010CF sends the required SIA handshake to the panel.
After receiving the handshake, the control panel transmits an alarm message in the SIA format.
The 3G4010CF/LE4010CF decodes and transforms the SIA events into an IP packet that it sends
to the central station receiver over the cellular network.
The central station's receiver acknowledges the alarm and sends a command to the 3G4010CF/
LE4010CF to generate the corresponding 2025Hz kiss-off signal for a minimum of one second.
After the 3G4010CF/LE4010CF generates a kiss-off signal, it sends the next alarm or, if no further
alarms need to be sent, the control panel goes on hook.
Note: The 3G4010CF/LE4010CF automatically adjusts the order of the handshakes based on
the last format the control panel used to transmit an event.
Inputs
The 3G4010CF/LE4010CF has four inputs that can be used to trigger specific communications.
These events transmit using the Contact ID or SIA format with Inputs 1-4 reporting as [991] to [994]
respectively.
Default settings are:
INPUT 1- AC LOSS
INPUT 2 - FIRE SUPERVISORY
INPUT 3 - FIRE ALARM
INPUT 4 - SYSTEM TROUBLE
Inputs can be configured as follows:
Normally Open - input activates when a short condition is detected between the terminal and COM
Normally Closed - input activates when an open condition is detected between the terminal and
COM
Single End of Line - input activates when a short or open condition is detected between the
terminal and COM and restores when a 5.6Kohm resistor is detected between the terminal and
COM.
Note: These inputs are programmable to communicate using either the Contact ID or SIA
format.
3G4010CF / LE4010CF Installation manual