15.3.3
Error type C
1
2
3
4
5
6
7
8
Fig. 55: Error type C, flowchart
6.0.0.0
E000
6.0.0.0
- - -
3/6
S
6.0.0.0
300
5/6
S
6.0.0.0
0
6/6
S
Fig. 56: Acknowledging error type C
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Program step/query
1
2
3
4
5
6
7
8
Table 31: Error type C
Acknowledging error type C:
To change to menu mode, press the operating button. Menu number <6.0.0.0> flashes on
the display.
Press the operating button again. Menu number <6.0.0.0> is displayed without flashing.
E000
The graphics show "- - -".
12.3
The units display shows the current incidence (x) as well as the maximum incidence of the
error (y) in the format "x/y". After 300 seconds, the figure for current incidence will increase
by one
E000
12.3
12.3
Wait until the remaining time is up.
If the current incidence (x) is the same as the maximum incidence of the error (y), the error
can be acknowledged manually.
Press the operating button again. The error is acknowledged, and the status page is dis-
played.
NOTICE
The error will be acknowledged automatically if the cause of the error is
eliminated.
Contents
Error code is displayed
Motor Off
Red LED On
Error criterion fulfilled?
> 5 min?
Error counter is increased
Error counter > 5?
SSM is activated
Error acknowledged?
End; auto control resumes
Yes
No