D
C
E
Fig. 16: Example of a foundation screwed
connection
7.4.2
Permitted installation positions
with vertical motor shaft
4 x 90°
Fig. 17: Permitted installation positions with
vertical motor shaft
7.4.3
Turn of motor impeller unit
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
min. 5 mm
min. 5 mm
min. 5 mm
Example of a foundation screwed connection
•
Align the complete unit when installing it on the foundation with the help of the spirit
level (at the shaft/discharge port).
A B
•
Always place shims (B) on the left and right adjacent to fasteners (e.g. stone screws (A))
between the baseplate (E) and base (D).
•
Evenly and firmly tighten the fixation material.
•
For distances > 0.75 m, support the baseplate at the centre between the fixation ele-
ments.
The permissible installation positions with a vertical motor shaft are shown in Fig. 17.
All installation positions except for "motor facing down" are allowed.
Discharge any condensate via the existing holes, pump lantern and motor.
For this purpose, remove the plug on the motor flange.
The motor impeller unit can be arranged in four different positions relative to the pump
housing (each offset by 90°).
The motor impeller unit consists of an impeller, lantern and motor with electronic module.
Motor supported
Pump housing supported, motor attached to
the base
Pump housing and motor supported
en