1
2
3
4
5
6
8
Fig. 50: Error type D, flowchart
6.0.0.0
E000
6.0.0.0
60
1/1
S
6.0.0.0
0
1/1
S
Fig. 51: Acknowledging error type A or D
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Program step/query
1
2
3
4
5
6
7
8
7
Table 29: Error type D
Acknowledging error types A or D:
•
To change to menu mode, press the operating button. Menu number <6.0.0.0> flashes on
the display.
•
Press the operating button again. Menu number <6.0.0.0> is displayed without flashing.
The time remaining before the error can be acknowledged is displayed.
•
Wait until the remaining time is up. The waiting time before manual acknowledgement is
always 60 seconds for error types A and D.
12.3
•
Press the operating button again. The error is acknowledged, and the status page is dis-
played.
Contents
•
Error code is displayed
•
Motor Off
•
Red LED On
•
SSM is activated
•
Error counter is increased
Is there a new type "A" fault?
> 1 min?
Error acknowledged?
Is there a new type "A" fault?
Branching to error type "A"
End; auto control resumes
Yes
No
en
161