en
No.
Name
1.0.0.0
Setpoint
2.0.0.0
Control mode
2.3.2.0
Δp-v gradient
3.0.0.0
Pump on/off
4.0.0.0
Information
4.1.0.0
Actual values
4.1.1.0
Actual values
sensor (In1)
4.1.3.0
Power
4.2.0.0
Operating data
4.2.1.0
Operating hours
4.2.2.0
Consumption
4.2.3.0
Countdown,
pump cycling
4.2.4.0
Time left until
pump kick
4.2.5.0
Mains On
counter
4.2.6.0
Pump kick
counter
4.3.0.0
States
4.3.1.0
Base-load pump
138
Type Symbol
Values/explanations
Setpoint adjustment/display
±
(for additional information, see section
"Adjusting the setpoint")
Control mode adjustment/display (for addi-
±
tional information, see section "Control
modes" and "Setting the control mode")
Constant speed control
Constant Δp-c control
PID-Control
Setting the gradient of Δp-v (value in %)
ON
±
Pump switched on
OFF Pump switched off
Information menus
Display of current actual values
Depending on current control mode.
Δp-c, Δp-v: Value H in m
PID-Control: Value in %
Current power input P
Display of operating data
Sum of the pump's active operating hours
(counter can be reset via infrared interface)
Energy consumption in kWh/MWh
Time until pump cycling in h (increments of
0.1 h)
Time until next pump kick (after a pump
downtime of 24 h (e.g. via "External off"),
the pump automatically runs for 5 s)
Number of switching-on procedures of the
supply voltage (each occasion the supply
voltage is established after an interruption
is counted)
Number of successful pump kicks
The value display statically shows the iden-
tity of the regular base-load pump. The
units display statically shows the identity of
the temporary base-load pump
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Display conditions
Not displayed for all pump types
Not displayed for constant speed
in W
1
The operating data refers to the
electronic module currently being
operated
Only displayed at the MA (main
pump) and for internal pump cyc-
ling. Can be set in the service menu
<5.1.3.0>
Only displayed if pump kick is activ-
ated
Only displayed if pump kick is activ-
ated
Only displayed at the MA (main
pump)