7.5.2
Condensate drainage/Insulation
116
DN
Forces F [N]
F
X
Values in acc. with ISO/DIN 5199 – class II (2002) – Appendix B
Table 6: Permissible forces and torques on pump flanges
Horizontal pump, top connector z-axis, case 1A
DN
Forces F [N]
F
X
Discharge flange
32
315
40
385
50
525
65
648
80
788
100
1050
125
1243
150
1575
Values in acc. with ISO/DIN 5199 – class II (2002) – Appendix B
Table 7: Permissible forces and torques on pump flanges
If not all working loads reach the maximum permitted values, one of these loads may exceed
the normal limit value. Provided that the following additional conditions are fulfilled:
•
All force and torque components are limited to 1.4 times the maximum permitted value.
•
The forces and torques acting on each flange meet the requirements of the compensation
equation.
Fig. 23: Compensation equation
Σ F
and Σ M
effective
(inlet and outlet). Σ F
mitted values of both pump flanges (inlet and outlet). The algebraic signs of Σ F and Σ M are
not taken into consideration in the compensation equation.
Influence of material and temperature
The maximum permissible forces and torques apply for the grey cast iron base material and
for an initial temperature value of 20 °C.
For higher temperatures, the values must be corrected as follows depending on the ratio of
their modulus of elasticity:
E
/ E
t, EN-GJL
20, EN-GJL
E
= Modulus of elasticity grey cast iron at the selected temperature
t, EN-GJL
E
= Modulus of elasticity grey cast iron at 20 °C
20, EN-GJL
When using the pump in air conditioning or cooling systems:
•
The condensate that forms in the lantern can be drained specifically via an existing
drilled hole. A drain pipe can also be connected to this opening and a small amount of
escaping liquid can be drained off.
•
The motors are equipped with condensation water holes which are closed with a rubber
plug at the factory. The rubber plug is used to guarantee that protection class IP55 is
fulfilled.
•
Installation position:
All installation positions except for "motor facing down" are allowed.
•
The air vent valve (Fig. I/II/III, Item 1.31) must always point upward.
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
F
F
Σ Forces F
Y
Z
F
F
Σ Forces F
Y
Z
298
368
578
350
438
683
473
578
910
595
735
1155
718
875
1383
945
1173
1838
1120
1383
2170
1418
1750
2748
are the arithmetic sums of the effective values of both pump flanges
effective
and Σ M
max. permitted
max. permitted
Torques M [Nm]
M
M
M
X
Y
Z
Torques M [Nm]
M
M
M
X
Y
Z
385
263
298
455
315
368
490
350
403
525
385
420
560
403
455
613
438
508
735
525
665
875
613
718
are the arithmetic sums of the maximum per-
Σ Torques M
Σ Torques M
560
665
718
770
823
910
1068
1278