Télécharger Imprimer la page

Wilo Stratos GIGA Notice De Montage Et De Mise En Service page 162

Publicité

Les langues disponibles

Les langues disponibles

en
15.3.2
Error type B
5
8
Fig. 52: Error type B, flowchart
Incidence X < Y
6.0.0.0
E000
6.0.0.0
75
3/6
S
Fig. 53: Acknowledging error type B (X < Y)
Incidence X = Y
6.0.0.0
E000
6.0.0.0
300
6/6
S
6.0.0.0
0
6/6
S
Fig. 54: Acknowledging error type B (X = Y)
162
Program step/query
1
1
2
2
3
4
3
5
6
4
7
8
6
Table 30: Error type B
Acknowledging error type B:
7
To change to menu mode, press the operating button. Menu number <6.0.0.0> flashes on
the display.
Press the operating button again. Menu number <6.0.0.0> is displayed without flashing.
The units display shows the current incidence (x) as well as the maximum incidence of the
error (y) in the format "x/y".
If the current incidence of the error is less than the maximum incidence:
Wait for auto reset time.
The value display shows the remaining time until auto reset of the error in seconds. After the
auto reset time has run out, the error will be automatically acknowledged and the status
page will be displayed.
12.3
If the current incidence of the error is equal to the maximum incidence:
Wait until the remaining time is up.
The time until manual acknowledgement is always 300 seconds. On the value display, the re-
maining time until manual acknowledgement of the error is displayed in seconds.
Press the operating button again. The error is acknowledged, and the status page is dis-
played.
12.3
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
NOTICE
The auto reset time can be set in menu number <5.6.3.0> (time input 10 to
300 seconds).
Contents
Error code is displayed
Motor Off
Red LED On
Error counter is increased
Error counter > 5?
SSM is activated
> 5 min?
> 5 min?
Error acknowledged?
End; auto control resumes
Yes
No

Publicité

loading

Ce manuel est également adapté pour:

Stratos giga-dStratos giga-b