Wilo Stratos GIGA Notice De Montage Et De Mise En Service page 123

Publicité

Les langues disponibles

Les langues disponibles

Name
Assignment
SBM
Individual run signal/collective run
signal, readiness signal and mains
On signal
SSM
Individual/collective fault signal
IF module interface
Terminals for serial, digital building
automation interface
Table 13: Terminal assignment
8.6
Differential pressure sensor con-
nection
8.7
Making the electrical connection
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Notices
Potential-free individual run signal/collective run signal (changeover con-
tact), operation readiness signal is available at the SBM terminals (menus
<5.1.6.0>, <5.7.6.0>).
Contact load:
minimum permissible: 12 V DC / 10 mA,
maximum permissible: 250 V AC / 24 V DC, 1 A
Potential-free single/collective fault signal (changeover contact) is avail-
able at the SSM terminals (menu <5.1.5.0>).
Contact load:
minimum permissible: 12 V DC / 10 mA,
maximum permissible: 250 V AC / 24 V DC, 1 A
The optional IF module is pushed into a multi-plug in the terminal box.
The connection is twist proof.
NOTICE
The terminals In1, In2, AUX, GND, Ext. off and MP meet the
EN 61800-5-1 "safe isolation" requirement
– to the mains terminals
– and to the terminals SBM and SSM (and vice versa).
The control features a PELV (protective extra low voltage) circuit design.
This means that the (internal) supply meets the supply requirements for
safe isolation, the GND is connected to protective earth (PE).
Stratos GIGA/-D
Table 14: Differential pressure sensor connection
Cable
Colour
1
Black
2
Blue
3
Brown
Table 15: Connection; differential pressure sensor cable
NOTICE
Guide the electrical connection for the differential pressure sensor
through the smallest threaded cable gland (M12) on the electronic mod-
ule.
For a twin-head pump or Y-pipe installation, connect the differential
pressure sensor to the main pump. The measuring points of the differen-
tial pressure sensor must be arranged in the collector pipe on the suction
and discharge side of the twin-head pump system.
Make the connections in accordance with the terminal allocation.
Earth the pump/installation as per regulations.
Reinstall any uninstalled safety devices, e.g. module cover!
Stratos GIGA B
Terminal
Function
In1
Signal
GND
Earth
+24 V
+24 V
en
123

Publicité

loading