The D component is set to zero at the factory because this setting is suitable for many ap-
plications.
Change the parameters in small steps only and monitor the effects on the system continu-
ously. Only a trained expert in the field of control engineering may carry out adjustment of
the parameter values.
Control component
P
I
D
Table 17: PID parameter
The sign for the P component determines the control's direction of control action.
Positive PID-Control (default):
If the P component is positive, the control system reacts to falling below the setpoint by in-
creasing the pump speed.
Negative PID-Control
If the P component is negative, the control system reacts to falling below the setpoint by re-
ducing the pump speed.
Carry out settings by turning and pressing the operating button. Turn the operating button
to the left or right to browse the menus or configure settings.
•
Rotate
: Menu selection and parameter setting.
•
Press
: Activation of menus or confirming settings.
The DIP switch is beneath the housing cover.
No.
Function
1
Switching between default and service mode. For additional information, see
section "Activating/Deactivating service mode"
2
Activating or deactivating access disable. For additional information, see sec-
tion "Activating/Deactivating access disable"
Table 18: DIP switch
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Factory setting
0.5
0.5 s
0 s
(= deactivated)
NOTICE
Possible malfunction in case of incorrect direction of control ac-
tion for PID control!
The pump runs only at minimum or maximum speed. It will not react to
changes in the parameter values.
• Check the controller's direction of control action.
Setting range
Incrementation
-30.0 ... 2.0
0.1
-1.99 ... 0.01
0.01
0.00 ... 1.99
0.01
2.0 ... 30.0
0.1
10 ms ... 990 ms
10 ms
1 s ... 300 s
1 s
0 ms ... 990 ms
10 ms
1 s ... 300 s
1 s