No.
Name
5.8.1.2
Pump kick time
interval
5.8.1.3
Pump kick speed
6.0.0.0
Error acknow-
ledgement
7.0.0.0
Access disable
Table 20: Menu structure
12
Decommissioning
12.1
Switching off the pump and tem-
porary shutdown
12.2
Shutdown and storage
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Type Symbol
Values/explanations
OFF
Pump kick is switched off
Can be set between 2 h and 72 h in 1 h
±
steps
Can be set between the pump's minimum
±
and maximum speeds
For additional information, see "Acknow-
±
ledging errors" section.
Access disable inactive (changes possible)
±
(for additional information, see section "Ac-
tivating/Deactivating access disable").
Access disable active (no changes possible)
(for additional information, see "Activating/
Deactivating access disable" section)
CAUTION
Risk of property damage due to overheating!
Hot fluids can damage the pump seals when the pump is at a standstill.
After deactivating the heat source:
• Allow the pump to run until the fluid temperature has dropped to an
CAUTION
Risk of property damage due to frost!
If there is a danger of frost:
• Drain the pump completely to avoid damage.
•
Close the shut-off device in the pressure pipe. If a non-return valve is installed in the
pressure pipe, and there is counter pressure, the shut-off device can remain open.
•
Do not close the shut-off device in the suction line.
•
Switch off the pump and allow it to drain completely. Ensure the coasting is smooth.
•
If there is no danger of frost, make sure the fluid level is sufficient.
•
Operate the pump every month for 5 minutes. Doing this prevents deposits from occur-
ring in the pump compartment.
WARNING
Risk of injury and damage to property!
• Dispose off the pump contents and rinsing fluid by taking the legal
• Always wear protective clothing, safety gloves and safety glasses
•
Clean the pump thoroughly prior to storage!
•
Drain the pump completely and rinse thoroughly.
•
The remaining fluid and rinsing fluid should be drained, collected and disposed off via
the drain plug. Observe local regulations along with the notes under "Disposal"!
•
Seal suction and discharge connection with caps.
•
After removal, store the pump in a dry, dust-free location.
appropriate level.
regulations into account.
when working.
Display conditions
Not displayed if pump kick was de-
activated
Not displayed if pump kick was de-
activated
Only displayed if there is an error.
en
143