Wilo Stratos GIGA Notice De Montage Et De Mise En Service page 122

Publicité

Les langues disponibles

Les langues disponibles

en
8.5
Terminal assignment
Name
Assignment
L1, L2, L3
Mains connection voltage
; (PE)
Protective earth conductor
In1
Actual value input
(1) (input)
In2 (input)
Setpoint input
GND (2)
Earth connections
+24 V
DC voltage for external consumer /
(3) (output)
signal transmitter
AUX
External pump cycling
MP
Multi Pump
Ext. Off
Control input "Overriding OFF" for
external, potential-free switch
122
Control terminals
Power terminals
Earth terminals
Table 12: Tightening torques for control, power and earth terminals
Fig. 29: Threaded cable connections
Notices
3~380 V AC – 3~440 V AC, 50/60 Hz, IEC 38
Type of signal: Voltage (0 ... 10 V, 2 ... 10 V)
Input resistance: R
Type of signal: Current (0 ... 20 mA, 4 ... 20 mA)
Input resistance: R
Can be configured in the service menu <5.3.0.0>
Connected at the factory via the M12 threaded cable gland, via In1 (1),
GND (2), + 24 V (3) according to the sensor cable names (1, 2, 3).
In2 can be used as input for remote setpoint adjustment in any operating
mode.
Type of signal: Voltage (0 ... 10 V, 2 ... 10 V) Input resistance: R
Type of signal: Current (0 ... 20 mA, 4 ... 20 mA) Input resistance: R
Can be configured in the service menu <5.4.0.0>
For both input In1 and In2
Load: max. 60 mA
The voltage is short-circuit proof.
Contact load: 24 V DC / 10 mA
Pump cycling can be performed using an external, potential-free contact.
If external pump cycling was activated previously, a single bypass of the
two terminals will perform a pump cycling. Rebypassing repeats this pro-
cess while maintaining the minimum runtime.
Parameterisable in service menu <5.1.3.2> Contact load: 24 V DC/10 mA
Interface for twin-head pump function
The pump can be switched on/off via the external potential-free contact.
In systems with higher switching frequency (> 20 switch-ons/switch-offs
per day) switch-off via "External off".
Parameterisable in service menu <5.1.7.0> Contact load: 24 V DC/10 mA
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA-D, Wilo-Stratos GIGA B • Ed.01/2024-02
Tightening torque
[Nm] ± 10 %
0.5
1.3
0.5
11 ... 22 kW:
M16 M12
M20 M40
≥ 10 kΩ
i
= 500 Ω
i
≥ 10 kΩ
i
= 500 Ω
i