To deactivate the Energy Manager function, select a different function (ALL / Permanent /
OFF / ON) and press the "Enter" key.
NOTE!
Notes on setting up the switch-on and switch-off points
If the difference between the switch-on and switch-off points is too small, or if there
are fluctuations in effective power, the result may be multiple switching cycles.
To avoid switching on and off frequently, the difference between the switch-on and switch-
off points should be at least 100 - 200 W.
When choosing the switch-off point, the power consumption of the connected consumer
should be taken into account.
When choosing the switch-on point, the weather conditions and anticipated insolation
should be taken into account.
Application example
Switch-on point = 2000 W, switch-off point = 1800 W
If the inverter is outputting 2000 W or above, then the floating switch contact on the inverter
is switched on.
If the inverter output falls to below 1800 W, the floating switch contact is switched off.
This allows useful applications, such as operating a heat pump or an air-conditioning sys-
tem using as much self-generated power as possible, to be implemented quickly
Time / Date
Set the time, date, the display format and automatic changeover between summer and
winter time
Setting range
Set time
Set the time (hh:mm:ss or hh:mm am/pm – depending on the setting for the time display
format)
Set date
Set the date (dd.mm.yyyy or mm/dd/yyyy - depending on the setting for the date display
format)
Time display format
For specifying the time display format
Setting range
Factory setting
Date display format
for specifying the date display format
Setting range
Factory setting
When the floating NO contact is off (open contact)
When the floating NO contact is on (closed contact)
Set time / Set date / Time display format / Date display format /
Summer/winter time
12hrs / 24hrs
Depends on country setup
mm/dd/yyyy or dd.mm.yy
Depends on country setup
31