Time/Date - Fronius Primo 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Primo 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Relay test
Function test to confirm whether the floating switch contact switches
Switch-on point (only if the "Energy Manager" function is activated)
to set the effective power limit from which the floating switch contact is
switched on
Factory setting
Setting range
Switch-off point (only if the "Energy Manager" function is activated)
to set the effective power limit from which the floating switch contact is
switched off
Factory setting
Setting range

Time/Date

Setting the time, date, display format, and automatic adjustment for daylight
saving time
Setting range
Set time
Setting the time (hh:mm:ss or hh:mm am/pm, depending on the setting under
Time display format)
GAF
As soon as "GAF" mode is selected, the relay will be switched
on. As soon as the power module reports an error and
switches from regular grid power feed operation to an error
state, the relay is opened. This way, the relay can be used for
fail safe functions.
Application example
When using single-phase inverters at a multi-phase location a
phase equalization might be necessary. If an error occurs with
one or more inverters and the connection to the grid is dis-
connected, the other inverters must also be disconnected in
order to maintain phase equilibrium. The "GAF" relay function
can be used with the datamanager or an external protective
device to detect or signal that an inverter is not being sup-
plied or is disconnected from the grid, and that the remaining
inverters should also be disconnected from the grid via re-
mote control.
Active output:
ON:
The floating NO switch contact is constantly switched on
while the inverter is operating (as long as the display lights up
or displays).
OFF:
The floating NO switch contact is switched off.
Energy Manager:
E-Manager:
You can find additional information on the "Energy Manager"
function in the following "Energy Manager" section.
1000 W
set switch-off point up to the inverter's nominal output
(W or kW)
500
0 up to the inverter's set switch-on point (W or kW)
Set time / Set date / Time display format / Date display
format / Daylight saving time
29

Publicité

Table des Matières
loading

Table des Matières