Version - Fronius Primo 3.0-1 Instructions De Service

Masquer les pouces Voir aussi pour Primo 3.0-1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Grid frequency limits:
Q-mode:
AC power limit including
SoftStart indicator and/
or AC grid frequency
derating:
AC voltage derating:

Version

Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
Display area
36
FILmax - upper inner grid frequency in Hz (Hertz)
FILmin - lower inner grid frequency in Hz (Hertz)
FOLmax - upper outer grid frequency in Hz (Hertz)
FOLmin - lower outer grid frequency in Hz (Hertz)
Indicates which reactive power setting is currently active on the
inverter (e.g. OFF, Q / P, etc.)
Max P AC - maximum output power, which can be changed us-
ing the "Manual Power Reduction" function
GPIS - Gradual Power Incrementation at Startup - indicates (%/
sec) whether the SoftStart function is active on the inverter
GFDPRe - Grid Frequency Dependent Power Reduction enable
limit - indicates the set grid frequency in Hz (Hertz) from when
power derating takes place
GFDPRv - Grid Frequency Dependent Power Reduction derat-
ing gradient - indicates the set grid frequency in %/Hz, how
strong power derating is
GVDPRe - Grid Voltage Depending Power Reduction enable
limit - threshold value in V from which voltage-dependent power
derating starts
GVDPRv - Grid Voltage Depending Power Reduction derating
gradient - derating gradient %/V with which the power is re-
duced
Message - indicates whether the dispatch of an info message
via Fronius Solar Net is active
Display / Display Software / Integrity Checksum / Memory Card
/ Memory Card #1 / Power Stage / Power Stage Software / EMI
Filter / Power Stage #3 / Power Stage #4

Publicité