BIN-IN
Configuration of the binary input
*
If the safety position is 0 or 100%, the actuator is completely vented or pressurized, respectively, as soon as the
relevant signal is applied to the binary input.
With the fast pressurizing/venting version, two valves are driven in each case in order to completely vent and
pressurize more rapidly.
Output
Option
Configuration of the output signals
Top Control Continuous
Selection of the function of
the binary input
Searching of a security
position
Binary input not activated
Enter the security position
(0..100%) *
Type of binary input
normally closed
(0..5 V = 1; 10..30 V = 0)
normally open
(0..5 V = 0; 10..30 V = 1)
End of the binary input
function
Setting the analogue output
(see next page)
Setting the binary output
(see next page)
End of the configuration of the output signals