Type 8691
DeviceNet
11.6.2. configuration of the pcB devicenet
Valve connection
Internal connection
Figure 33:
DeviceNet PCB
11.6.3. Bus connection (circular connector m12 x 1, 5-pole, male)
The control head features a 5-pole micro-style circular connector.
The following configuration conforms to the DeviceNet specification.
pin
1
signal
Shielding
Table 14:
Pin assignment circular plug-in connector DeviceNet
Pin 4: CAN_H
Data lines
Figure 34:
View of plug from the front onto the pins, the soldered connections are behind
11.7. Terminating circuit for devicenet systems
When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct.
The circuit prevents the occurrence of interference caused by signals reflected onto the data lines.
The trunk line must be terminated at both ends with resistors of 120 Ω each and 1/4 W power loss
(see "Figure 35: Network topology, DeviceNet").
2
V +
white
Pin 5: CAN_L
blue
Pin 1: Drain
(Shield)
LED – pilot valve (yellow)
Device status LED (two-colored: red/green)
Bus LED (two-colored: red/green)
DIP switches for
bus address and baudrate
3
4
V –
CAN_H
Pin 3: V–
black
Pin 2: V+
red
5
CAN_L
Supply voltage
11 ... 25 V DC
max. power 3 W,
if valve is switched
english