Type 8691
AS-Interface installation
Figure 29:
Teach function
When the teach function is activated the actuator cannot be actuated via the AS-Interface communication.
Pilot valve LED (yellow)
Status LED:
flashes yellow when teach function is running
Key in recess for actuating the teach function (keep
pressed for approximately 5 seconds
Chronological description of the teach function:
• the bottom end position is read in internally
• the pilot valve switches
• the actuator moves automatically to the top end position
• the top end position is read in internally
• the pilot valve is turned off
• the actuator moves back to the bottom end position
english