Type 8691
Technical data
6.7.2.
electrical data with as-interface bus control
Connections
Supply voltage
Outputs
Max. switching capacity
Watchdog function
devices without external supply voltage:
Max. power consumption
Power consumption input during normal operation
(after current reduction;
valve + 1 end position reached)
devices with external supply voltage:
External supply voltage
The power supply unit must
include a secure disconnection in
accordance with IEC 364-4-41
(PELV or SELV)
Max. power consumption
Max. power consumption from AS-Interface
6.7.3.
electrical data with devicenet bus control
Connections
Supply voltage
Max. power consumption
Output
Pull-in current current
Holding current
Circular plug-in connector (M12 x 1, 4-pole)
29.5 V – 31.6 V DC (according to specification)
1 W via AS-Interface
integrated
120 mA
90 mA
24 V ± 10 %
55 mA (after current reduction ≤ 30 mA)
55 mA
Circular plug-in connector (M12 x 1, 5-pole)
11 V – 25 V
< 80 mA
≤ 50 mA
≤ 30 mA