Setting the baud rate
Adapting the control head to the baud rate of the network.
DIP 7
DIP 8
Baud rate
off
off
125 kBaud
on
off
250 kBaud
off
on
500 kBaud
on
on
not allowed
ATTENTION!
Any change to the settings using the DIP switches will only become effective
following a re-start of the device.
A re-start can be carried out by briefly unclamping and the re-clamping the control head
from/to the network or by sending a corresponding Reset Message. It is also possible be
switching the network power supply off and then on again.
Configuration of the Process Data
3 static inputs and 3 static output assemblies are available for the transmission of the process data via an
I/O connection. Selected attributes are gathered together in one object in these assemblies, in order to be
able to be transmitted together as process data via an I/O connection.
The process data can either be accessed cyclically in the connection variants "Polled I/O" and "Bit-strobed
I/O" with "Change of State" when the input values change, or non-cyclically via Explicit Messages.
The access path for non-cyclic access is:
With the Get_Attribute_Single service, non-cyclic read access can be obtained to the input data, and non-
cyclic write access to the output data with Set_Attribute_Single.
1 Data Byte for inputs (sensors and/or proximity switches):
Bit
Sensor
Bit 0
S1 (Prox.switch 1)
Bit 1
S2 (Prox. switch 2)
Bit 2
S3 (Terminal for additional prox. switch)
Bit 3 ... Bit 7
Not used
1 Data Byte for inputs (sensors and/or proximity switches):
Bit
Sensor
Bit 0
S1 (Valve 1)
Bit 1
S2 (Valve 2)
Bit 2
S3 (Valve 3)
Bit 3 ... Bit 7
Not used
I
NSTALLATION AND
class
4
instance
1
attribute
3
Value allocation
0 Prox. switch 1 OFF
1 Prox. switch 1 ON
0 Prox. switch 2 OFF
1 Prox. switch 2 ON
0 Prox. switch 3 OFF
1 Prox. switch 3 ON
0 always
Value allocation
0 Valve 1 OFF
1 Valve 1 ON
0 Valve 2
1 Valve 2
0 Valve 3
1 Valve 3
0 always
C
OMMISSIONING
OFF
ON
OFF
ON
1066 - 27