Check that the seal is correctly positioned in the body casing.
noTe!
damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Screw the body casing in all the way.
Close the device (assembly tool: 674077
Figure 37:
Position of the seal in the body casing
please note:
if the settings are changed by actuating the dip switches, this change will not take effect until the
device is restarted.
For a restart
• briefly disconnect the control head from the supply voltage and reconnect or
• switch the supply voltage off/on or
• transmit an appropriate reset message.
11.10. configuration of the process data
To transmit process data via an I/O connection, 1 static input and 1 static output assembly can be selected. These
assemblies contain selected attributes combined into one object so that process data can be transmitted collectively
via an I/O connection.
Process data can be accessed
• cyclically in the connection variants "Polled I/O" and "Bitstrobed I/O", with "Change of state", if input values
change, or
• acyclically via Explicit Messages.
The access path for acyclical access is:
With the Get_Attribute_Single service the input data can be accessed acyclically for reading.
With the Set_Attribute_Single service the output data can be accessed acyclically for writing.
The assembly tool (674077) is available from your Bürkert sales office.
10)
48
).
10)
english
Body casing
Seal
Body casing
class
4
instance 1
attribute 3
Type 8691
DeviceNet

Publicité