Input and output signals to the higher-level control (PLC):
Pin 3 - S1 out
Pin 4 - S2 out
Pin 5 - S3 out
Pin 6 - S4 out
Pin 7 - Y1
Fig. 5:
Multipole connection 24 V DC
(12-pole circular plug-in connector M12 x 1.0 - male according
to IEC 61076-2-101 — view onto the plug pins)
An external initiator can be connected via the triple terminal strip 2
(see "Fig. 4" or see Operating Instructions, chapter "Connecting
an external initiator").
16
Pin 2 - GND
11
Pin 1 - 24 V
10
12
Pin 9 - Y3
Pin 8 - Y2
english
Type 8681

AS-I design

9
AS-I DESIGN
9.1

Connection options

Connection left:
1 x M16 x 1.5 cable gland with multipole connection (M12
plug according to IEC 61076-2-101, 4-pole) to an 8 cm or
80 cm long cable
Connection right:
1 x M16 x 1.5 cable gland for external initiator
9.2
Number of connectable control
heads
In AS interface versions with extended addressing range (A/B slave),
1 master can communicate with 62 slaves.
In AS interface versions with addressing range 31 slaves, a maximum
of 31 control heads can be connected to a bus line (the address
range restriction).
9.3

Bus line length

The bus cable may be a maximum of 100 m long. When designing the
system, consider the length of the round cable leading directly to the
control head (see example calculation in the Operating Instructions).