Assembly; Pneumatic Installation - Burkert 8681 Guide Rapide

Masquer les pouces Voir aussi pour 8681:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.2

Assembly

For the assembly of the control head Type 8681 to a process valve,
you will require a process valve-specific hub flange as an adapter.
The hub flange must be adapted to the design of the process valve.
Mount the piston rod with the target on the process valve
spindle. Observe reference dimensions!
Fasten the hub flange on the process valve. During this, observe
central alignment and sealing conditions!
Check the secure fit of the sealing rings (in the upper and the
lower groove).
Mount the control head on the hub flange (infinitely 360°
rotatable).
Secure the control head with the two locking screws (shoulder
screws M5, tightening torque: max. 3.2 Nm) in the middle
groove of the hub flange against unintentional removal (not
fixed into position! – see "Fig. 1" or Operating Instructions,
chapter "Assembly").
7.3

Pneumatic installation

Connect the required working connections 2/A1 to 2/A3 (each
according to model) with the corresponding connections on
the process valve - see "Fig. 2" or in the Operating Instructions
Type 8681.
Connect the supply line to supply pressure connection 1/P
(2.5 ... 8 bar).
12
english
Type 8681
Assembly / Installation
A silencer has already been mounted on the exhaust air port
(3/R) in the supplied state.
Lead seal
lugs at
the housing
3/R
Exhaust air port
(silencer)
2/A3: SV 3
2/A2: SV 2
2/A1 ... A3 - working ports of solenoid valves (SV)
Fig. 2:
Pneumatic connections
The flow restriction screws R and P
of the solenoid valves (see Operating
Instructions) are used for setting the
air intake and exhaust for the working
ports (for setting of the control speed of
the process valves).
Fig. 3:
Flow restriction screws of the
solenoid valves
1/P
Supply pressure
connection
2/A1: SV 1
open
closed
R
P

Publicité