Function Of The Dip Switches - Burkert 8791 Manuel D'utilisation

Masquer les pouces Voir aussi pour 8791:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 8791
Operating
9.3.2
function of the Dip switches
On
1 2 3 4
DiP Switches Position
1
ON
OFF
2
ON
OFF
3
ON
OFF
4
ON
OFF
Factory setting can be changed via communications software.
6)
Characteristic type can be changed via communications software.
7)
Table 9:

Function of the DIP switches

information about the communications software:
The switching position of the DIP switch has priority over the communications software!
If the values of the sealing function (CUTOFF) or the correction characteristic (CHARACT) are changed
via the communication software, the corresponding function must be active (DIP switch set to ON).
The effective direction of the set-point value (DIR.CMD) can be changed via the Dip switches.
Function
Reversal of the effective direction of the set-point value (DIR.CMD)
(set-point value 20 – 4 mA corresponds to position 0 – 100%)
Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position 0 – 100%)
Sealing function active. The valve completely closes below 2%
opens above 98% of the set-point value (CUTOFF)
No sealing function
Correction characteristic for adjustment of the operating character-
istic (Linearization of the operating characteristic CHARACT)
Linear characteristic
MANUAL operating status manual
AUTO AUTOMATIC operating status
6)
and
7)
english