Type 8791
Functions
entering the freely programmable characteristic
The characteristic is defined by 21 nodes distributed uniformly over the position set-point values ranging from 0 –
100%. They are spaced at intervals of 5%. A freely selectable stroke (adjustment range 0 – 100%) is assigned to
each node. The difference between the stroke values of two adjacent nodes must not be greater than 20%.
example of a programmed characteristic
Valve stroke [&]
100
90
80
70
60
50
40
30
20
10
0
10
20
Figure 15:
Example of a programmed characteristic
10.1.4 INPUT -
enter the input signal
Under this menu option, enter the unit signal used for the set-point value.
Factory setting: 4 – 20 mA
30
40
50
60
70
4 – 20 mA
0 – 20 mA
Unit signal [%]
80
90 100
english