Electrical Connection Of The Pumps; Connection Of Three-Phase Pumps; Connection Of Single-Phase Pumps With Internal Capacitor; Connection Of Single-Phase Pumps With External Capacitor - DAB E.Box Plus Instructions Pour L'installation Et La Maintenance

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 119
R-N
I: 11-12
Q1: 14-15
Q2: 16-17
Q3: 18-19
FU2 - FU3
FU5
FU4
The supply voltage of the E.BOX PLUS panel must be the same as that of the pumps used. For example, if the panel is fed
with a supply voltage of 3~400V the pumps must be at 3~400V.
The E.BOX BASIC panel must be fed with a supply voltage of 1~230V. The pumps must be single-phase 230V.
Connect the earth cables of the pumps to the earth terminals in the E.Box panel! Make sure that all the cables have adequate
dimensions for the currents they have to bear.
If the single-phase pump needs an external capacitor, it can be placed inside the panel.
If 2 pumps are used, they must be identical.
Attention, an incorrect electrical connection could damage the E.Box panel.
2.2

Electrical connection of the pumps

Connection of three-phase pumps

Three-phase pumps can be connected only to the E.box Plus. They must be connected to the terminals P1 and P2 as shown in
Figure 3. The correct sequence of phases U, V and W must be respected so that they turn in the correct direction.

Connection of single-phase pumps with internal capacitor.

The pumps must be connected to the terminals P1 and P2 shown in Figure 3. The neutral wire must be connected to the terminal N, the phase
wire must be connected to the terminal with a screenprinted L.

Connection of single-phase pumps with external capacitor.

Pumps with an external capacitor must be connected to the terminals P1 and P2 shown in Figure 5. Particular care must be taken to respect the
correspondence between the screenprinting and the names of the pump wires. The pump cable marked C must be connected to terminal C. The
same applies to cables A and P. See Figure 3.
The pump capacitor can be placed inside the E.box panel, on the metal bracket provided.
Terminals connecting digital alarm inputs
Sensor input connection terminal
Terminals connecting the alarms Q1, Q2, Q3.
Panel protection fuses (Plus version only)
Pump P2 protection fuse (Plus version only)
Pump P1 protection fuse (Plus version only)

Figure 3: Electrical connection of pumps

ENGLISH
69

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E.box plus dE.box basicE.box basic d

Table des Matières