WHERE TO INSTALL THE PANEL:
It is good practice to install the panel correctly, taking particular care to comply with the following indications.
the panel must be kept in a completely dry place, far from sources of heat;
−
the electric panel must be perfectly closed and isolated from the outside environment, so as to avoid the entry of insects, humidity and dust
−
which could damage the electrical components, jeopardising their regular operation.
Choose the sensors with a grade of protection suitable for the place in which they will be positioned.
−
1.1
Technical characteristics
Power supply
+10% - 15%
Frequency
Grade of protection
No. pumps that can be connected:
Maximum rated current of the pumps
Maximum rated power of the pumps
Environment temperature
Storage temperature
Air relative humidity
Max. altitude:
1.2
Protections
The panel is self-protected and protects the electropumps against:
overloads and excess temperature with automatic reset,
−
short circuits with fuses (only Plus model),
−
excess currents in pumps (overload protection),
−
abnormal voltages,
−
lack of phase and thermal protection KK,
−
dry operation,
−
rapid starts,
−
faults of the pressure sensor,
−
inconsistency of floats and/or probes,
−
blocking of the pumps.
−
2
INSTALLATION
Strictly respect the electric supply values indicated on the electrical data plate.
Although it has a grade of protection IP55, it is not advisable to use it in an atmosphere charged with oxidising or corrosive
−
gases.
The panels must be protected against the direct rays of the sun and against unfavourable weather conditions.
−
Use good quality cables with a section suitable for the current required by their motors and for their length. Pay particular
−
attention to the power cable which must carry the current for all the pipes connected.
The sensors must be suitable for the place in which they are positioned.
−
It is necessary to take suitable steps to keep the temperature inside the panel within the "limits of environment temperature
−
use" listed below.
High temperatures can lead to accelerated ageing of all the components, resulting in more or less severe malfunctions.
−
It is also recommended that the person carrying out installation should ensure the cable clamps are watertight.
−
Accurately tighten the cable clamps where the power cable enters the panel and those of any external controls, connected
−
by the installer, so as to ensure that the cables cannot work loose from the clamps.
ENGLISH
E.box Plus
E.box Plus D
3 x 400V
3 x 230 V
1 x 230V
50/60Hz
IP 55
1 or 2
12A
5.5kW at 3 x 400V
3.2kW at 3 x 230V
2.2kW at 1x230V
-10 ÷ 40°C
-25°C ÷ 55°C
50% at 40°C
90% at 20℃
1000 m (a.s.l.)
Table 1: Technical data
65
E.box Basic
E.box Basic D
1 x 230V
50/60Hz
IP55
1 or 2
12A
2.2kW at 1 x 230V
10 ÷ 40°C
-25°C ÷ 55°C
50% at 40℃
90% at 20℃
1000 m (a.s.l.)