Conditions D'utilisation Pour La Certification Ul Du Psd1-M - Parker PSD1 Manuel D'installation

Table des Matières

Publicité

2.10.4.

Conditions d'utilisation pour la certification UL du PSD1-M

Catégorie
certifié
PSD1-M:
Vous trouverez dans ce chapitre
• Certification UL ......................................................................................................................... 21
• Installations- & Environmental Characteristics PSD1-M ............................................................ 21
• PSD1-M Installations- & Environmental Characteristics ............................................................ 22
• Conditions of utilization for CSA certification ............................................................................. 24
2.10.4.1
Certification UL
Spécification
Numéro fichier E : E142140
L'homologation UL est uniquement valable si la plaque d'identité de l'appareil contient le
symbole "UL" .
UL508C, 3ième édition, dernière révision 9 novembre 2010.
C22.2 No.274-13, 1ière édition, publiée mars 2013
2.10.4.2
Installations- & Environmental Characteristics
PSD1-M
• The devices are only to be installed in a pollution degree 2 environment
(maximum).
• Maximum Surrounding Air Temperature 40 °C.
• The devices must be appropriately protected (e.g. by a switching cabinet). - Open
type equipment.
• Temperature rating of field installed conductors shall be at least 60°C. Do only
use copper lines.
Do only use the Parker cables available under Accessories (voir page 95) or
assemble the cables according to the specified regulations.
• Control voltage supply (24 VDC) only permissible with "class 2" power supply.
• The devices are internally protected against overvoltage in compliance with
UL508C.
• The drive modules are equipped with a current limit. Values for maximum device
current and maximum motor current can be set via PSD ServoManager (Chapter
resp. Menu Limit values & Motor Characteristics).
• PSD1-M is intended for use in motors with internal or external motor protection
Integral motor overload protection is not available.
• Motor overheating protection is not supported and must externally be realized.
• Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
Manufacturer Instructions, National Electrical Code and any additional local codes
• Protective earth of the motor must be connected to protective earth of the device.
Please observe that ground on PSD1 - motor connector is, according to
NEC NFPA 70, a functional earth and not a protective earth.
193-011006N8 2019-11
193-011006N8 PSD1 Manuel d'installation
25.11.19 14:26
21 (126)