Risk of Electric Shock, wait at least 10 minutes before removing cover.
Connecting protective earth
Connect protective earth via a copper wire of minimum
10 mm
of the PSD1M (axis controller) and of the mains module
PSD1-M_P:
24 (126)
Conditions of utilization for CSA certification
2.10.4.4
External Overvoltage Protection
External overvoltage protection in accordance with Canadian Standards
C22.2-No.274-13 with over-voltage protection device (VZCA2) CSA-certified.
Note the following table:
Model No
(Quantity 1)
OVR T2 3N
40-440 P(TS)U
BSPM 4480 WY NGR
904 346
Ground rail not sufficient
For CSA approval, earth rail must be replaced by a direct earth connection.
Removing the earth rail (4) (Right):
1
24 VDC
2
GND 24 VDC
3
DC power supply bus -
4
Protective earth
5
DC power supply bus +
by means of the provided screws at the bottom
2
193-011006N8 2019-11
Maximum
Voltage
Continuous
Protection
Operating
Rating
Voltage (Vac)
(VPR)(Vpk)
L-GND
L-GND
420 Veff Max
1500 V Max
L-L
L-L
840 Veff Max
3000 V Max
L-GND
L-GND
660 Veff Max
2500 V Max
L-L
L-L
770 Veff Max
2500 V Max
25.11.19 14:26
Category
/
Nominal earth
leakage current
1
/
10 kA
1
/