HNS 3000
7.5
SETTING RANGES FOR THE WINDOW FUNCTION
Rod length
Measuring range
in cm
in cm
25.0
17.8
28.0
20.8
37.0
29.8
41.0
33.8
52.0
44.8
73.0
65.8
Rod length
Measuring range
in inch
in inch
9.85
7.00
11.05
8.15
14.60
11.70
16.15
13.30
20.50
17.60
28.8
25.9
Lower switch value in °C *
-23.0 .. +97.8
Lower switch value in °F *
-9 .. +208
* All ranges given in the table can be adjusted by the increments shown and apply when the
offset is zero.
7.6
SETTING RANGES FOR THE OFFSET
Rod length
in cm
25.0
28.0
37.0
41.0
52.0
73.0
Rod length
in inch
9.85
11.05
14.60
16.15
20.50
28.8
* All ranges shown in the table can be adjusted by the increments shown.
Version 2018/07/06
Lower switch value
in cm *
0.3 .. 17.4
0.4 .. 20.4
0.5 .. 29.2
0.6 .. 33.2
0.7 .. 44.0
1.0 .. 64.6
Lower switch value
in inch *
0.15 .. 6.85
0.15 .. 8.00
0.20 .. 11.45
0.20 .. 13.05
0.30 . 17.25
0.4 .. 25.4
Upper switch value in °C *
-22.2 .. +98.6
Upper switch value in °F *
-8,0 .. +209
Measuring range
in cm
17.8
20.8
29.8
33.8
44.8
65.8
Measuring range
in inch
7.00
8.15
11.70
13.30
17.60
25.9
HYDAC ELECTRONIC GMBH
Upper switch
value
in cm*
0.4 .. 17.6
0.5 .. 20.5
0.7 .. 29.5
0.8 .. 33.4
1.0 .. 44.3
1.5 .. 65.1
Upper switch
value
in inch *
0.20 .. 6.90
0.20 .. 8.05
0.30 .. 11.55
0.30 .. 13.15
0.40 .. 17.40
0.6 .. 25.6
Increment in °C
0.2
Increment in °F
1
Setting range
Offset in cm *
0.0 .. 71.2
0.0 .. 83.2
0.0 .. 119.2
0.0 .. 135.2
0.0 .. 179.2
0.0 .. 263.2
Setting range
Offset in inch *
0.00 .. 28.00
0.00 .. 32.60
0.00 .. 46.80
0.00 .. 53.20
0.00 .. 70.40
0.0 .. 103.6
Page 13
Increment
in cm *
0.1
0.1
0.1
0.1
0.1
0.1
Increment
in inch*
0.05
0.05
0.05
0,05
0.05
0.1
Increment
in cm *
0.1
0.1
0.1
0.1
0.1
0.1
Increment
in inch*
0.05
0.05
0.05
0,05
0.05
0.1
Part No. 669927