6.3. SETTING THE SWITCHING POINTS AND SWITCH-BACK POINTS /
HYSTERESES
Press appropriate key
Switching point/switch-back point/hysteresis number is displayed e.g. "S.P. 1"
After 2 seconds the current setting flashes.
Using the "+" and "–" keys, alter the setting.
After 3 seconds the display switches back.
6.3.1 Setting a switching point
SP1
press ON key
display
6.3.2 Setting a hysteresis
(Only possible if the switch-back mode is set to "hysteresis".)
SP1
press OFF key display
6.3.3 Setting a switch-back point
(Only possible if the switch-back mode is set to "switch-back point")
SP1
press OFF key display
Notes:
If "LOC" appears in the display when trying to alter the settings, programming
is disabled. Corrective action: set hardware and software programming
enable to "ON". (See Point 9 "Programming enable")
If the "+" or "–" key is held down during alteration, the value automatically
advances in larger increments.
If a setting has been altered, "PROG" appears briefly in the display when the
display switches over. The new setting is then saved in the unit.
2 s
set switching point
= larger value
2 s
set hysteresis
= larger value
2 s
set switch-back point
= larger value
temperature
display
3 s
= smaller value
temperature
display
3 s
= smaller value
temperature
display
3 s
= smaller value
E