Example for switch output 1 (normally closed and normally open function):
E
Normally open function
Normally closed function
Abbreviations:
Notes:
• It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP). In the case of low SPs we recommend setting the RP
first.
• The window function only works properly (switching on and off) if all switch
values (including the safety margin) are above 0 bar and below the nominal
pressure range.

7.2 Setting ranges for the switch outputs

Measuring range Lower limit of
in bar
0 .. 25
0 .. 40
0 .. 100
0 .. 250
0 .. 400
0 .. 600
* All ranges given in the table can be adjusted by the increments shown.
Status: 04.04.2018
P
P
Aus
Aus
FH1 plus 0,4%FS
FH1
FH1
Ein
Ein
Off
FL1
FL1
FL1 minus 0,4%FS
FNO
FNO
Ein
Ein
On
Schließerfunktion
Schließerfunktion
Aus
Aus
Off
FNC
FNC
On
Ein
Ein
Öffnerfunktion
Öffnerfunktion
Aus
Aus
Off
"FH1", "FH2"
= upper switch value 1 / upper switch value 2
"FL1", "FL2"
= lower switch value 1 / lower switch value 2
"FNO"
= normally open when window function is active
"FNC"
= normally closed when window function is active
Upper limit of
RP / FL
SP / FH
in bar
in bar
0.25
0.4
1.0
100.0
2.5
250.0
4
400
6
600
HYDAC ELECTRONIC GMBH
On
Sicherheitszone
Sicherheitszone
Safety zone
Ein
Ein
On
Sicherheitszone
Sicherheitszone
Safety zone
Aus
Aus
Off
Minimum
difference
between RP
and SP
or FL and FH
25.00
0.25
40.0
0.4
1.0
2.5
4
6
EDS 8000
Rückschaltwert
Rückschaltwert
Reverse switch point
Schaltwert
Schaltwert
Switch point
Schaltwert
Schaltwert
Switch point
Rückschaltwert
Rückschaltwert
Reverse switch point
t
t
Increment
in bar
0.05
0.1
0.2
0.5
1
1
Part No.: 669758