Setting Ranges For The Switch Outputs - HYDAC ELECTRONIC EDS 820 Notice D'utilisation

Manocontacteur electronique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EDS 820 IO-Link
Example for switching output 1 (N/C and N/O function):
FH1 plus 0,4%FS
FL1 minus 0,4%FS
Schließerfunktion
Schließerfunktion
Normally open function
Normally closed function
Öffnerfunktion
Öffnerfunktion
Abbreviations: "FH1", "FH2" = upper switch value 1 / upper switch value 2
"FL1", "FL2" = lower switch value 1 / lower switch value 2
"FNO"
"FNC"
NOTES:
• It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP).
• The window function only works properly (switching on and off) if all switch
values (including the safety margin) are above 0 bar and below the nominal
pressure range.

10.2 Setting ranges for the switch outputs

Measuring
Untere
range
Grenze von
RP / FL
in bar
in bar
0 .. 25
0.25
0 .. 40
0.4
0 .. 100
1.0
0 .. 250
2.5
0 .. 400
4
0 .. 600
6
* All ranges shown in the table can be adjusted by the increments shown.
Edition: 2014-07-11
P
P
Aus
Aus
On
Safety zone
Sicherheitszone
Sicherheitszone
FH1
FH1
Off
Ein
Ein
FL1
FL1
Safety zone
Sicherheitszone
Sicherheitszone
FNO
FNO
On
Ein
Ein
Aus
Aus
Off
FNC
FNC
On
Ein
Ein
Off
Aus
Aus
= N/O when window function is active
= N/C when window function is active
Upper limit of
SP / FH
in bar
25.00
40.0
100.0
250.0
400
600
HYDAC ELECTRONIC GMBH
Reverse switch point
Rückschaltwert
Rückschaltwert
Switch point
Schaltwert
Schaltwert
Ein
Ein
On
Switch point
Schaltwert
Schaltwert
Rückschaltwert
Rückschaltwert
Reverse switch point
Off
Aus
Aus
t
t
Min. difference
betw.
RP and SP
or FL and FH
0.25
0.4
1.0
2.5
4
6
9
E
Increment*
in bar
0.05
0.1
0.2
0.5
1
1
Part No.: 669916

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

669916

Table des Matières