Drop line lengths
Baud rate
Maximum length of a drop line
125 kBaud
250 kBaud
500 kBaud

Safety setting for bus failure

In case of a bus failure, the setting of the last data byte of the bus outputs will be retained as long as
power is connected.

Electrical connection

The bus line is a 4-pole cable with an additional screen that must correspond to the DeviceNet
specifications and over which both information (data) and power (power supply for the low-power actuators
and sensors) will be transmitted.
Bus connection (round plug M12, 5-pole)
CAN_H
white
Data
CAN_L
lines
blue
Drain (screen)
not used
Plug viewed from the front looking at the pins (not at the solder side).
The Type 1066 control head has a 5-pole Micro-style M12 round plug. The following pin configuration
corresponds to the DeviceNet specification:
Pin
Signal
1
Screen
2
V+
3
V-
4
CAN_H
5
CAN_L
Termination circuit for DeviceNet systems
When installing a DeviceNet system, attention must be paid to the correct termination circuit for the data
lines. This circuit prevents interference arising from signal reflection on the data lines. The main line must
therefore be terminated as both ends, as shown, with resistors of 120 Ω with 1/4 W power rating.
Max. accumulated length in the network
6 m
6 m
6 m
V-
black
V+
red
Colour
not used
red
black
white
blue
I
C
NSTALLATION AND
OMMISSIONING
156 m
78 m
39 m
Voltage supply
11 ... 25 V DC
max. power 5 W, if all
valves switched
(3 x Type 6510 with 1 W each)
1066 - 25