DeviceNet

Explanation of terms

• DeviceNet is a field bus system that is based on the CAN protocol (Controller Area Network). It makes
possible the networking of actuators and sensors (slaves) with a master control unit (master).
• In the DeviceNet, the Type 1066 control head is a slave device according to the Predefined
Master/Slave Connection laid down in the DeviceNet specification. Polled I/O, Bit Strobed I/O and
Change of State 4 (COS) are supported as I/O connection types.
• In DeviceNet, a differentiation is made between cyclic or event-controlled transmitted process messages
of higher priority (I/O Messages) and non-cyclic management messages of lower priority (Explicit Mes-
sages).
• The protocol corresponds to DeviceNet Specification Release 2.0
NOTE
A diskette with configuration files (BUE1066.EDS and BUE1066.ICO) is always delivered
with the DeviceNet models. You can also obtain these files over the Internet.

Technical data

Baud rate
Adresses
Process data
Inputs
Files

Maximum line lengths

The maximum total line lengths (sum of main and drop lines) of a network depend on the baud rate.
Total line lengths according to the DeviceNet specification
Baud rate
125 kBaud
250 kBaud
500 kBaud
1)
According to the DeviceNet specification. When using another cable type, lower maximum values
apply (refer to the DeviceNet specification).
24 - 1066
125 kBit/s, 250 kBit/s, 500 kBit/s (via DIP switch);
Factory setting: 125 kBit/s
0 ... 63 (via DIP switch);
Factory setting: 63
2 static input assemblies
(Input: from control head 1066 to DeviceNet Master/Scanner)
1 static Output Assembly
3 sensors (proximity switches) S1 - S3, pnp, plus-switching
Supply via the DeviceNet line (11 to 25 V DC)
Switching level High signal
Switching level Low signal ≤ 1.5 V
BUE1066.EDS
BUE1066.ICO
You can also obtain these files over the Internet.
Maximum total line length when using Thick Cables according to the
DeviceNet specification
1)
≥ 5 V
500 m
250 m
100 m